Analysis of Age Transformer Due to Annual Load Growth in 20 kV Distribution Network

dc.contributor.authorindra roza1, yussa ananda2, lisa adriana siregar3, catra indra cahyadi4, junaidi
dc.date.accessioned2023-10-15
dc.date.available2023-10-15
dc.date.issued2021
dc.identifier.uri https://sinta.kemdikbud.go.id/journals/profile/10904?q=Analysis+of+Age+Transformer+Due+to+Annual+Load+Growth+in+20+kV+Distribution+Network
dc.description.abstract Distribution transformer is a component in distributing electricity from distribution substations to consumers. Damage to distribution transformer causes continuity of customer service to be disrupted. The length of the PLN electricity network requires a transformer to distribute electricity to serve consumers. The curves of daily peak loads for housing, shops and factories / industries vary. The 200 kVA distribution transformer load cannot serve housing, shops and factories / industries. The method used is the replacement of a distribution transformer with a capacity of one stage greater or the replacement of a distribution transformer with a capacity of two levels larger. The distribution transformer carried out by the research is a capacity of 200 kVA replaced by 250 kVA. The ability of a distribution transformer cannot accommodate a load which will increase as an area is advanced. Observations made by calculating the age of the transformer by assuming the annual load growth (r) = 3% = 0.3. Annual peak load (P) = 1.8 p, u increase in oil temperature at peak load (θo = 96.21 0C; 84.16 0C). The increase in the hottest temperature above the oil cover, the increase in the temperature of the hottest place above the oil (θg = 20 0C; 20 0C). The ratio of the load loss to the nominal load excitation loss (Q = 3; 30). By assuming the values of these methods it can be estimated that the life of a distribution transformer is 20 kV, a capacity of 200 kVA is 18 yearsen_US
dc.language.isoenen_US
dc.publisherUniversitas Harapan Medanen_US
dc.subjecttransformer due to annual load growth in 20 kv en_US
dc.titleAnalysis of Age Transformer Due to Annual Load Growth in 20 kV Distribution Networken_US
dc.typeKarya Ilmiahen_US


File In This Item

No Thumbnail
Name 758943ec03e82b0aac2ec23899375029artjur _ junaidi.pdf
Size 296010 Mb
Format application/pdf
Description fulltext
Fulltext

This item appears in the following Collection(s)

Karya Ilmiah [1420]

Show Simple Item Record